Purpose    

This document outlines the procedure and strategy for Campus Planning & Facilities Management (CPFM) thermal management and operations within University buildings.


Responsibilities    

CPFM Facilities BAS/Mechanical Shop Personnel


Scope                                               

This standard applies to all General Funded University buildings. 


Statement

Following accepted standards for managing the thermal environment will benefit the University by providing clear expectations for occupant thermal comfort, while reducing energy consumption. Additionally, establishing consistent methodology will ensure a work setting that safeguards building resources and assets.  


Details

1.    Applicability

     1.1.    This Applicability

  • This policy applies to all General Funded University buildings.

...

  • Housing and Athletics facilities are governed by separate policies.

...

2.    Temperature Temperature Ranges (Setpoints)2.1.    Standard

  • Standard building hours when the campus is open for business (unlocked and accessible) are typically 7:30am-8:00pm, Monday-Friday.

...

  • Unlocked and accessible periods (open for business) are considered as “occupied”.

...

  • Locked and non-accessible periods (closed for business) are considered as “unoccupied”. 

...

  • Buildings with central heating and cooling systems:

      ...

        • Occupied Building Hours (open) - Temperature setpoints range between 70°F (heating on) and 75°F (cooling on).

      ...

        • Unoccupied Hours (Closed) – Temperatures may be allowed to drop to 66°F or increase to 78°F.

       
      2.3.    Buildings Buildings ventilated naturally (heating only):2.3.1.    Occupied

        • Occupied Building Hours – Temperature setpoints are typically set to 70°F.

      ...

        • Unoccupied Hours (Closed) – Temperatures may be allowed to drop to 66°F.              

      2.4.    Variances 
      2.4.1.    Research Variances

      • Research space temperatures will be addressed

      ...

      • individually
      • Requests for variances shall be submitted to CPFM who will coordinate with EHS for investigation and approval.

      3.    Reporting Reporting Malfunctions or Uncomfortable Conditions3.1.    Occupants

      ...

      • Occupants who find this standard produces an uncomfortable environment are requested to contact CPFM Work Control  Center @ 541-346-2319, or workcontrolcenter@uoregon.edu.

      4.    Window Window Management4.1.    Occupants

      • Occupants are encouraged to responsibly manage manually operated windows by ensuring windows are closed when leaving the space or during adverse weather conditions.

      ...

      5.    Prohibited Prohibited Accessory Equipment5.1.    Accessory

      • Accessory electric heaters must meet current university safety and energy standards - DO NOT purchase or bring any space heaters from home.

      ...

      • If necessary, accessory space heaters must be approved and purchased by CPFM Facilities Services Electrical shop at Departmental expense.

      ...

      • Service calls resulting from use of non approved devices will be charged to the responsible Department.

      ...

      • Contact CPFM Work Control Center @ 541-346-2319, or workcontrolcenter@uoregon.edu with all questions or concerns related to auxiliary heating appliances.

      ...

      User-installed portable or window-mounted air conditioning units are prohibited.

      5.3.    Look Look for Space Heaters at https://safety.uoregon.edu/safetysheets 

      6.    Contact Contact Information 6.1.    Address

      ...

      View file