OVERVIEW
Building Automation Systems (BAS) Too Hot/Cold Work Order Management. Following this procedure will provide consistent and efficient management of work orders regarding too hot/cold calls.
ROUTING ROUTINE TOO HOT/COLD CALLS THROUGH WCC
Facilities Services (FS) Work Control Center (WCC) receives initial issue/request and creates a work order (WK).
Requests come from these sources:
- Phone calls
- Email requests
- Web requests https://cgis.uoregon.edu/Calllog (email workcontrolcenter@uoregon.edu for access)
WCC staff should use the following script to gather the necessary information from the requester:
Expand |
---|
Contact Information
WCC will create a call log entry, for the work order, with some unique handling, based on appropriate problem code. |
BAS Electrical Problem Codes
- BAS Controls (High priority must be dispatched)
- Hot/Cold (High priority must be dispatched)
- P1 Renos (all P1's are dispatched)
- P3 Renos
BAS Electrical account set-up RXBLDS 23555
BAS is the first responders for hot/cold calls, who will triage and determine if the root cause is controls or mechanical in nature.
If controls in nature, the BAS Department will perform the work
- BAS may ask for a phase addition for the controls contractor
- The controls contractor index is RXBLDS 23555
- BAS may ask for a phase addition for the controls contractor
If mechanical in nature, the BAS ECST will contact Work Control via phone, email, radio or WCC AiM notes with pertinent details associated with the parent work order.
- Work Control will create a phase addition for the mechanical shop to perform repairs, as needed. If urgent Work Control will dispatch the mechanical shop.
- Mechanical shop index is RBSYS 23555.
ROUTING URGENT TEMPERATURE ISSUES
Expand | ||
---|---|---|
| ||
|
Document Hot/Cold Work Orders Step-By-Step Guide:
Unique work orders are created for all issues. No generic or annual work orders are allowed for these types of issues.
If parts are required, the ECST will make notes in the WK for status, and submit a purchase request (PREQ) to order the parts.
ADDITIONAL INFORMATION
If campus requestors inquire about an Air Conditioner or Heater send the below reply emails:
Air Conditioner
Expand |
---|
Greetings, XXX, If you are still interested, please let us know the room number(s) involved and what index you would like to use once approved. Thank you, |
Heaters (safety sheet)
Expand |
---|
Greetings, XXX, If you are still interested, please let us know the room number(s) involved and what index you would like to use once approved. Thank you, |
Freezer Alarms
There is a notification program set up with the occupants. Work Control needs to ask for an index for any updates to this program.List of Buildings BAS Does Not/Or Partially Services for Hot/Cold Call (need to be assigned to Mechanical)
Expand | ||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|